; PROFIBUS configuration ;
; ;
; This file configures a pyprofibus instance. ;
; ;
; ----------------------------------------------- ;
; General settings
[PROFIBUS]
; Enable/disable debug mode.
; 0 -> no debugging.
; 1 -> DP debugging.
; 2 -> DP and PHY debugging.
debug=0
; PHY protocol layer configuration
[PHY]
; The PHY layer driver type.
type=serial
; The PHY device name/path.
; Can be a device like /dev/ttyS0 or /dev/ttyAMA0 for 'serial'.
dev=/dev/ttyS0
; The Profibus on-wire baud rate.
baud=19200
; Serial line flow control and handshaking
rtscts=False
dsrdtr=False
; FDL protocol layer configuration
[FDL]
; DP protocol layer configuration
[DP]
; The master device class. Either 1 or 2.
master_class=1
; The Profibus address of this device.
master_addr=2
; ---
; Slave configurations
; Add as many [SLAVE_xxx] sections as needed.
; ---
; First slave configuration
[SLAVE_0]
; This slave's Profibus address
addr=8
; The path to the GSD file.
gsd=si03806a.gse
; Boolean: Sync mode enabled/available?
sync_mode=1
; Boolean: Freeze mode enabled/available?
freeze_mode=1
; 8 bit integer specifying the Profibus group ident mask.
group_mask=1
; This slave's watchdog timeout, in milliseconds.
watchdog_ms=300
; Module configuration.
; For each module plugged into the slave, add a module_xxx
; entry with the name of the module.
; The module name must match the name from the GSD file (approximately).
; The modules are used in the order of the index number.
module_0=6ES7 138-4CA01-0AA0 PM-E DC24V
module_1=6ES7 132-4BB30-0AA0 2DO DC24V
module_2=6ES7 132-4BB30-0AA0 2DO DC24V
module_3=6ES7 131-4BD01-0AA0 4DI DC24V
; The number of output bytes this slave transmits to the
; master in Data_Exchange.
; This usually depends on the modules plugged into the slave.
output_size=2
; The number of input bytes this slave expects to receive
; in Data_Exchange.
; This usually depends on the modules plugged into the slave.
input_size=1
|